2 -
Checking the battery charging system
To check the current flow of the recharging circuit, use the “DDS” diagnosis instrument, which is equipped with an inductive clamp-type amperemeter: refer to chapter “Testing the battery charging system”, Sect. 6 - 11
With the DDS diagnosis instrument you can determine the engine rpm required for the alternator to produce sufficient current to charge the battery, feed the injection/ignition system and all the electrical equipment on the motorcycle. When applied to a cable, the clamp-type amperemeter detects the magnetic field generated by the current passing through that cable.
The tester performs an automatic calibration routine using its own transducer. If the measured current is a positive quantity, it means that generator is feeding all electric items and charging battery at the same time. A negative value means that charging system is not powering the loads and a significant amount of current must be supplied by the battery, which is discharging at the time of the measurement.
Or it is possible to use a multimeter (Sect. 6 -11, Diagnostic instruments); connect the multimeter probes to the battery terminals, select the DC scale on the instrument and check for the presence of 14.5 V±0.5 at an engine speed of 3000 rpm.
Important
If polarity is reversed when clamping the ammeter onto the cable, the sign of the readings will also be reversed, giving rise to incorrect diagnosis.
Recharging the battery
Examine the label on the battery showing the check intervals in order to determine when to test the voltage.
Charge the battery if the open circuit voltage is lower than 12.8 V. Leaving the battery discharged for more than one month could damage it. Check the battery charge with a voltmeter.
Always check the condition of the battery before recharging and 1 to 2 hours afterwards.
Important
Pay careful attention to recharging times. Stop charging immediately if the battery becomes too hot to the touch. Leave to cool before resuming charging.
 
Use only constant-voltage battery chargers.
Check that battery terminals are properly connected to the battery charger.
To charge the battery, proceed as follows.
 
Use fast charging in emergencies only.
Storing the battery
If the battery voltage is less than or equal to 11.5 V, it must be recharged.
Connect the battery charger to the battery.
Use a voltage of 16-17 V.
If the ammeter shows no change, increase the voltage to the maximum of 25 V.
Charge for 5 minutes.
If the ammeter shows a change, return the voltage to 16-17 V; otherwise replace the battery.
Topping up the electrolyte
Warning
Before carrying out any operations on the battery, keep in mind the safety standards (Sect.1 - 3, General safety rules). The electrolyte in the battery is toxic and can cause burns if it comes into contact with the skin because it contains sulphuric acid. Wear protective clothing, a face-mask and goggles when adding electrolyte. If the liquid comes into contact with the skin, wash thoroughly with cold water. If it comes into contact with the eyes, wash thoroughly with water for 15 minutes and consult an ophthalmologist. In the event of accidental ingestion, drink large quantities of water or milk, and continue with milk of magnesia, beaten egg or vegetable oil. Do not allow sparks, flames, cigarettes or any other heat source to come near the battery, as it produces explosive gases. When recharging or using the battery indoors, make sure that the room is adequately ventilated. Do not inhale the gases produced during recharging. KEEP OUT OF REACH OF CHILDREN.
 
Place the battery on a flat surface. Remove the protective film (1).
Warning
Make certain that the electrolyte is of the specific type for your battery.
 
Remove the container with the electrolyte from the plastic bag. Remove the cap strip (3) from the container (2).
 
Important
Keep the cap strip (3) to hand because it will be used later as plugs for the battery cells.
Warning
Do not peel or perforate the sealed areas.
 
Place the electrolyte container (2) upside down. Align the six sealed elements with the six filler holes on the battery. Push the container (2) downwards with sufficient force to break the seals and allow the liquid to flow out.
Note
Do not tilt the electrolyte container as this could interrupt the flow temporarily or even permanently.
 
Make certain that air bubbles emerge from all six filler holes. Leave the container in this position for at least twenty minutes.
If no bubbles emerge from one of the holes, tap gently on the bottom of the respective container.
Important
Never move the container away from the battery. Do not cut or puncture the liquid container.
 
Make sure that all the electrolyte has flowed out. Carefully extract the container (2) from the battery.
Fit the cap bar (3) -previously removed from the electrolyte container (2)- to the battery, ensure the caps plug off all filler holes.
3 -12 Ah batteries: leave to stand for at least 30 min.
12 Ah batteries: leave to stand for at least 1 hour.
Rest the cap strip on the filler holes without fixing it. Recharge the battery as described in the paragraph “Recharging the bat­tery”.
Note
When using an automatic reduction battery charger, check that the charger current (ampere) is equal or higher than the value of standard charging system (STD) indicated on the battery itself.
 
Press firmly downwards with both hands until the caps are firmly in place (do not use a hammer).
Battery
Battery safety rules
Warning
Before carrying out any operations on the battery, keep in mind the safety standards (Sect.  1 - 3, General safety rules). When under charge, batteries produce explosive gases. Keep batteries away from heat sources, sparks or open flames.
Instructions for use
The battery is a sealed, maintenance-free type and therefore requires no servicing installation.
Note
Always keep the battery clean. Apply grease around the battery terminal clamps to prevent corrosion.
Warning
Never remove the valve cover located on top of the cover. If the block, cover or terminals are broken or if the valve cover has been tampered with it is absolutely necessary to replace the battery.
Important
If the motorcycle is left unused for more than 30 days, remove the battery and store it in a safe, cool place.
 
Always charge the battery before the first operation and after long storage periods – such as before selling the vehicle.
Removal of the battery
Undo the screw (1) and remove the battery retaining bracket (2).
Loosen screws (3), remove the positive cable (4) and the (ABS) positive cable (5) from the positive terminal, and the negative cable (6) from the negative terminal, always starting from the negative (-) one, and remove the battery (7) by pulling it upwards.
 
Refitting the battery
Fit battery (7) on the relevant support, connect the positive cable (4) and the ABS positive cable (5) to the positive terminal, and the negative cable (6) to the battery negative terminal, always starting from the positive (+) one, and start the screws (3).
Check that the contacts are not oxidised and tighten the screws (3) of the terminals to a torque of 10 Nm ± 10%, applying wa­terproof spray.
Place the battery fixing bracket (2) and tighten the screw (1) to a torque of 5 Nm ± 10%.
 
Alternator
It is equipped with a 12 V, 500 W alternator, consisting of a fixed element (stator, A) located on the generator cover and of a movable element (rotor, B) fixed to the crankshaft.
Note
To check the battery charging system for faults, use the DDS diagnosis instrument and follow the instructions given in the para­graph, “Testing the battery charging system“ (Sect. 6 - 11).
 
The absolute value of voltage measured across the terminals of two of the three yellow cables (the measured value will be the same whichever combination of cable is used) must be within the range indicated in the table below.
(Ambient temperature: 20 °C)
Important
Before testing, disconnect the alternator wiring from the electrical system when the ignition key is set to OFF.
 
V effective
34±5
104±10
Values significantly lower than those indicated above can be due to:
-
-
In the above cases the whole alternator assembly (rotor and stator) should be renewed.
If checks have a favourable outcome, reconnect the alternator to the regulator with ignition key on OFF. Make sure that no cables are damaged or disconnected.
Removal of the alternator
Disconnect the cables of the alternator-side electric system (Sect. 6 -1, Routing of wiring on frame).
Remove the generator cover, the stator (A) and the rotor (B) (Sect. 9 - 8, Removal of the generator cover).
Refitting the alternator
Fit the rotor (B), the stator (A) and the alternator-side crankcase cover.
Connect the cables of the generator side electric system (refer to the table in chapter “Routing of wiring on frame”, Sect. 6 - 1).
 
 
Rectifier-regulator
The regulator (1) is placed on the rear right side of the vehicle under the semi-tail guard.
The rectifier/regulator consists of an aluminium casing containing the diodes that rectify the current produced by the alternator. It also contains an electronic device that regulates the current supplied by the alternator in accordance with battery voltage.
If the battery is drained, the current has the value necessary to restore optimum operating conditions of the battery. In contrast, if the battery is fully charged, the current value will be lower.
Note
Control the charger current by using the DDS diagnosis instrument (Sect. 6 - 11, Diagnostic instruments).
Removal of the regulator
Disconnect the voltage regulator connector (2) and the alternator connector (3) from the rectifier (1).
Undo the two fixing screws (4) of the regulator (1) and remove it together with them.
Important
Do not disconnect the battery cables when engine is running because this would cause irreparable damage to the regulator.
 
Refitting the regulator
Position the regulator (1) on the support.
Tighten the screws (4) to a torque of 10 Nm ± 10% (Sect. 3 - 3, Frame torque settings).
Important
Do not disconnect the battery cables when engine is running because this would cause irreparable damage to the regulator.
 
Connect the voltage regulator connector (2) and the alternator connector (3) to the rectifier.
 
Regulator fuse
The 30 A fuse placed inside the solenoid starter on the rear RH subframe protects the electronic rectifier.
 
Remove the fuse cap (A) to reach it.
A blown fuse can be identified by breakage of the inner filament (B)
Important
To avoid possible short circuits, replace the fuse in key OFF condition.
Warning
Never use a fuse with a rating other than the specified value. Failure to observe this rule may damage the electric system or even cause fire.
 
1